Turbo 200 Wiring Installation Instructions

50 + 7.5 MFD

50_7.5
Note: Not all installations have two (2) wires connected to the common as shown in the dual-value illustrated examples. In some installations there is only one (1) wire which is common to the compressor and fan motor.

EXAMPLE: To replace a 50 + 7.5 microfarad
Dual-Value Capacitor: BEFORE YOU START: Make note of the wires which are
attached to the fan motor (F), common (C), and compressor (Herm) terminals of
the capacitor being replaced. STEP 1: To achieve the 50.0 microfarad for the
compressor (HERM) - using two (2) jumper wires (a) connect the 5 (6) + 25, then
(b) connect 25 + 20.  This will equal 50.0
microfarads. Connect one of the wires from the compressor to the 25 MFD
terminal. STEP 2: Connect the other wire(s) from the compressor to the common
(C). [The common is the center black terminal]. STEP 3: Using one (1)
jumper wire, connect the 2.5 (3.0) + 5(4). 
This will equal 7.5 microfarads.  STEP 4: Connect one of the fan wires to the 5
(4) mfd terminal. STEP 5: Connect the other wire from the fan motor to the
common (C). [The common is the center black terminal].