Turbo 200 Wiring Installation Instructions

55 + 10 MFD

55_10
Note: Not all installations have two (2) wires connected to the common as shown in the dual-value illustrated examples. In some installations there is only one (1) wire which is common to the compressor and fan motor.

EXAMPLE: To replace a 55 + 10 microfarad
Dual-Value Capacitor: BEFORE YOU START: Make note of the wires which are
attached to the fan motor (F), common (C), and compressor (Herm) terminals of
the capacitor being replaced. STEP 1: To achieve the 55 microfarad for the
compressor (HERM) - using three (3) jumper wires (a) connect the 5 (4) + 5 (6),
then (b) connect the 5 (6) + 25, then (c) connect 25 + 20, this will equal 55.0
microfarads. Connect one of the wires from the compressor to the 25 MFD
terminal. STEP 2: Connect the other wire(s) from the compressor to the common
(C). [The common is the center black terminal]. STEP 3:  Connect one of the fan wires to the 10 mfd
terminal. STEP 4: Connect the other wire from the fan motor to the common (C).
[The common is the center black terminal].