Turbo 200 Wiring Installation Instructions

60 + 5 MFD

60_5
Note: Not all installations have two (2) wires connected to the common as shown in the dual-value illustrated examples. In some installations there is only one (1) wire which is common to the compressor and fan motor.

EXAMPLE: To replace a 60 + 5 microfarad
Dual-Value Capacitor: BEFORE YOU START: Make note of the wires which are
attached to the fan motor (F), common (C), and compressor (Herm) terminals of
the capacitor being replaced. STEP 1: To achieve the 55 microfarad for the
compressor (HERM) - using three (3) jumper wires (a) connect the 5 (4) + 25,
then (b) connect the 25 + 20, then (c) connect 20 + 10, this will equal 60.0 microfarads.
Connect one of the wires from the compressor to the 25 MFD terminal. STEP 2:
Connect the other wire(s) from the compressor to the common (C). [The common is
the center black terminal]. STEP 3:  Connect
one of the fan wires to the 5 (6) mfd terminal. STEP 4: Connect the other wire
from the fan motor to the common (C). [The common is the center black
terminal].