Turbo 200 Wiring Installation Instructions

62.5 + 5 MFD

62.5_5
Note: Not all installations have two (2) wires connected to the common as shown in the dual-value illustrated examples. In some installations there is only one (1) wire which is common to the compressor and fan motor.

EXAMPLE: To replace a 62.5 + 5
microfarad Dual-Value Capacitor: BEFORE YOU START: Make note of the wires which
are attached to the fan motor (F), common (C), and compressor (Herm) terminals
of the capacitor being replaced. STEP 1: To achieve the 55 microfarad for the
compressor (HERM) - using four (4) jumper wires (a) connect the 2.5 (3.0) + 10,
then (b) connect the 10 + 20, then (c) connect 20 + 25, then (d) connect the 25
+ 5 (4) this will equal 62.5 microfarads. Connect one of the wires from the
compressor to the 25 MFD terminal. STEP 2: Connect the other wire(s) from the
compressor to the common (C). [The common is the center black terminal]. STEP
3: Connect one of the fan wires to the 5 (6) mfd terminal. STEP 4: Connect the
other wire from the fan motor to the common (C). [The common is the center
black terminal].