For Turbo200X Wiring Instructions Click Here

Turbo 200 Wiring Installation Instructions

20 + 4 MFD

Screen_shot_2014-01-09_at_9.26.54_pm
Note: Not all installations have two (2) wires connected to the common as shown in the dual-value illustrated examples. In some installations there is only one (1) wire which is common to the compressor and fan motor.

EXAMPLE: To replace a 20 + 4.0 microfarad Dual-Value Capacitor:
BEFORE YOU START: Make note of the wires which are attached to the fan
motor (F), common (C), and compressor (Herm) terminals of the capacitor
being replaced.
STEP 1: To achieve the 20.0 microfarad for the compressor (HERM) - Connect
one of the wires from the compressor to the 20 MFD terminal.
STEP 2: Connect the other wire(s) from the compressor to the common (C).
[The common is the center black terminal].
STEP 3: Connect one of the fan wires to the 5 (4) MFD terminal.
STEP 4: Connect the other wire from the fan motor to the common (C). [The
common is the center black terminal].