Turbo 200 Wiring Installation Instructions

15 + 7.5 MFD

15_7.5
Note: Not all installations have two (2) wires connected to the common as shown in the dual-value illustrated examples. In some installations there is only one (1) wire which is common to the compressor and fan motor.

EXAMPLE: To replace a 15 + 7.5
microfarad Dual-Value Capacitor:

BEFORE YOU START: Make note of the wires which are attached to the fan

motor (F), common (C), and compressor (Herm) terminals of the capacitor

being replaced.

STEP 1: To achieve the 15 microfarad for the compressor (HERM) – Using one (1)
jumper wire, connect the 5 (6) + 10. 
This will equal 15 microfarads. 
STEP 2:  Connect one of the wires
from the compressor to the 10 MFD terminal. STEP 3: Connect the other wire(s)
from the compressor to the common (C). [The common is the center black
terminal].

STEP 3: To obtain the 7.5 microfarad for the fan (F), using one (1) jumper

wire connect the 5 (4) + 2.5 (3.0) . This will equal 7.5 microfarads. STEP 3:
Connect one of the fan wires to the 5.0 (4.0) MFD terminal.

STEP 4: Connect the other wire from the fan motor to the common (C). [The

common is the center black terminal].