For Turbo200X Wiring Instructions Click Here

Turbo 200 Wiring Installation Instructions

17.5 + 4 MFD

17.5_4
Note: Not all installations have two (2) wires connected to the common as shown in the dual-value illustrated examples. In some installations there is only one (1) wire which is common to the compressor and fan motor.

EXAMPLE:
To replace a 17.5 + 4 microfarad Dual-Value Capacitor: BEFORE YOU
START: Make note of the wires which are attached to the fan motor (F), common
(C), and compressor (Herm) terminals of the capacitor being replaced. STEP 1:
To achieve the 17.5 microfarad for the compressor (HERM) - Using two (2)
jumper wires, (a) connect the 5 (6) + 2.5 (3.0), then (b) connect the
2.5 (3.0) + 10.  This will equal 17.5 microfarads.  STEP 2: 
Connect one of the wires from the compressor to the 10 MFD terminal. STEP
3: Connect the other wire(s) from the compressor to the common (C). [The common
is the center black terminal]. STEP 3: Connect one of the fan wires to the
5 (4) MFD terminal. STEP 4: Connect the other wire from the fan motor to
the common (C). [The common is the center black terminal].