Turbo 200 Wiring Installation Instructions

25 + 4 MFD

25_4
Note: Not all installations have two (2) wires connected to the common as shown in the dual-value illustrated examples. In some installations there is only one (1) wire which is common to the compressor and fan motor.

EXAMPLE: To replace a 25 + 4.0 microfarad
Dual-Value Capacitor: BEFORE YOU START: Make note of the wires which are
attached to the fan motor (F), common (C), and compressor (Herm) terminals of
the capacitor being replaced.STEP 1: To achieve the 25.0 microfarad for the
compressor (HERM) - Connect one of the wires from the compressor to the 25 MFD
terminal. STEP 2: Connect the other wire(s) from the compressor to the common
(C). [The common is the center black terminal]. STEP 3: Connect one of the
fan wires to the 5 (4.0) MFD terminal.STEP 4: Connect the other wire from the
fan motor to the common (C). [The common is the center black terminal].