Turbo 200 Wiring Installation Instructions

27.5 + 10 MFD

27.5_10
Note: Not all installations have two (2) wires connected to the common as shown in the dual-value illustrated examples. In some installations there is only one (1) wire which is common to the compressor and fan motor.

EXAMPLE: To replace a 27.5 + 5.0
microfarad Dual-Value Capacitor: BEFORE YOU START: Make note of the wires which
are attached to the fan motor (F), common (C), and compressor (Herm) terminals
of the capacitor being replaced. STEP 1: To achieve the 27.5 microfarad for the
compressor (HERM) - using one (1) jumper wire connect the 25 + 2.5 (3.0). This
will equal 27.5 microfarads. Connect one of the wires from the compressor to
the 25 MFD terminal. STEP 2: Connect the other wire(s) from the compressor to
the common (C). [The common is the center black terminal]. STEP 3: Connect
one of the fan wires to the 10.0 MFD terminal. STEP 4: Connect the other
wire from the fan motor to the common (C). [The common is the center black
terminal].