Turbo 200 Wiring Installation Instructions

30 + 4 MFD

30_4
Note: Not all installations have two (2) wires connected to the common as shown in the dual-value illustrated examples. In some installations there is only one (1) wire which is common to the compressor and fan motor.

EXAMPLE: To replace a 30.0 + 4.0 microfarad
Dual-Value Capacitor: BEFORE YOU START: Make note of the wires which are
attached to the fan motor (F), common (C), and compressor (Herm) terminals of
the capacitor being replaced. STEP 1: To achieve the 30.0 microfarad for the
compressor (HERM) - using one (1) jumper wire connect the 20 + 10. This will
equal 30.0 microfarads. Connect one of the wires from the compressor to the 20
MFD terminal. STEP 2: Connect the other wire(s) from the compressor to the
common (C). [The common is the center black terminal]. STEP 3: Connect one
of the fan wires to the 5.0 (4.0) MFD terminal. STEP 4: Connect the other wire
from the fan motor to the common (C). [The common is the center black
terminal].