Turbo 200 Wiring Installation Instructions

40 + 10 MFD

40_10
Note: Not all installations have two (2) wires connected to the common as shown in the dual-value illustrated examples. In some installations there is only one (1) wire which is common to the compressor and fan motor.

EXAMPLE: To replace a 40* + 10 microfarad
Dual-Value Capacitor: BEFORE YOU START: Make note of the wires which are
attached to the fan motor (F), common (C), and compressor (Herm) terminals of
the capacitor being replaced. STEP 1: To achieve the 40.0 microfarad for the
compressor (HERM) - using one (1) jumper wire connect the 25 + 20. NOTE: *This will
equal 45.0 microfarads, however it is o.k. to use for 40mfd.
Connect one of the
wires from the compressor to the 25 MFD terminal. STEP 2: Connect the other
wire(s) from the compressor to the common (C). [The common is the center black
terminal]. STEP 3: Connect one of the fan wires to the 10 MFD terminal. STEP 4:
Connect the other wire from the fan motor to the common (C). [The common is the
center black terminal].