For Turbo200X Wiring Instructions Click Here

Turbo 200 Wiring Installation Instructions

42.5 + 4 MFD

42.5_4
Note: Not all installations have two (2) wires connected to the common as shown in the dual-value illustrated examples. In some installations there is only one (1) wire which is common to the compressor and fan motor.

EXAMPLE: To replace a 42.5 + 4.0 microfarad
Dual-Value Capacitor: BEFORE YOU START: Make note of the wires which are
attached to the fan motor (F), common (C), and compressor (Herm) terminals of
the capacitor being replaced. STEP 1: To achieve the 42.5 microfarad for the
compressor (HERM) - using three (3) jumper wires (a) connect the 2.5 (3.0) + 10,
then (b) connect the 2.5 (3.0) + 5 (6), then (c) connect the 5 (6) +25. This
will equal 42.5 microfarads. Connect one of the wires from the compressor to
the 25 MFD terminal. STEP 2: Connect the other wire(s) from the compressor to
the common (C). [The common is the center black terminal]. STEP 3: Connect
one of the fan wires to the 5 (4) MFD terminal. STEP 4: Connect the other wire
from the fan motor to the common (C). [The common is the center black
terminal].