Turbo 200 Wiring Installation Instructions

47.5 + 5 MFD

47.5_5
Note: Not all installations have two (2) wires connected to the common as shown in the dual-value illustrated examples. In some installations there is only one (1) wire which is common to the compressor and fan motor.

EXAMPLE: To replace a 47.5 + 5
microfarad Dual-Value Capacitor: BEFORE YOU START: Make note of the wires which
are attached to the fan motor (F), common (C), and compressor (Herm) terminals
of the capacitor being replaced. STEP 1: To achieve the 47.5 microfarad for the
compressor (HERM) - using two (2) jumper wires (a) connect the 2.5 (3.0) + 20,
then (b) connect 25 + 20.  This will
equal 47.5 microfarads. Connect one of the wires from the compressor to the 25
MFD terminal. STEP 2: Connect the other wire(s) from the compressor to the
common (C). [The common is the center black terminal]. STEP 3: Connect one
of the fan wires to the 5.0 (6.0) mfd terminal. STEP 4: Connect the other wire
from the fan motor to the common (C). [The common is the center black
terminal].